::: COMPANY NAME :::
|
|
| |
|
|
| |
Newsroom Overview
Please feel free to e-mail or call any of the contacts listed.

......................................................
|
|
| |
|
|
| |
Financial News

......................................................
|
|
| |
|
|
| |
Product & Service News
Neel launches a new product in the market.

......................................................
|
|
| |
|
|
| |
Events
Powerlux wins the "Best Product Appreciation Award" at Elecrama 2006

......................................................
|
|
| |
|
|
| |
|
|
| |
|
|
| |
|
|
| |
|
|
| |
|
|
|
| |
|
| |
UNINTERRUPTED POWER SUPPLY SYSTEM
State-of-the-art ONLINE UPS with
foreign collaboration from "Neelkanth".
|
|
"The smartest way to tackle power failure"
True on-line double conversion micro-controller based UPS system for high end servers, workstations, CAD/CAM...sensitive to AC power irregularities and blackout. The high switching frequency of the UPS enables fast response to dynamic loads like CNCs, textile and printing equipment, glass processing, medical equipments..., resulting in good transient response for non-linear loads. The UPS is designed to support advanced electronic equipments with high crest factor demand and provides unmatched performance.
|
|
| Salient Features |
 |
Efficiency |
Inverter Efficiency Overall Efficiency
|
Better than 95%
Better than 92% |
 |
Protection |
Rectifier |
I/P AC over/under voltage
DC over voltage
Battery charging over current
Single phase failure
Reverse phase sequence |
| |
|
Inverter |
O/P over voltage
O/P overload
O/P short circuit
DC under voltage
Over temperature |
 |
Metering |
LCD / LED display to read following parameters with user friendly mimic diagram:
I/P Voltage, O/P Voltage, Battery Voltage, I/P Current, O/P Current, Battery Charge, I/P Frequency, O/P Frequency
|
 |
Controls |
Input On/Off MCB/MCCB, By - Pass on/off switch, Output on/off switch, Manual by - pass switch, Inverters on/off |
 |
Physical |
Enclosure
Cable Entry
Colour |
IP 31 (IP 42-optional)
Bottom (top-optional)
Broken White/Siemens
Grey (optional as per req.) |
 |
Enviornment |
0 to 45° C max, upto 95% RH (non - condesing) |
| |
|
Cooling
Audible Noise
Altitude |
Forced air-cooling
<60dB upto 100KVA
<75dB upto 500KVA
<300 mtr. above MSL |
 |
Refference Standards |
IEC 146-(IV), EN 50091-1, EN 50091-2 |
 |
Optional Features |
Remote Start-Stop, RS 232/485 interface CNC machine interlock |
|
| Technical Specifications |
| |
 |
Input |
Voltage |
230 VAC, (+15%-20%)Single Phase 415 Volts (+15%-20%) 3 Phase 4 wire |
| |
|
Frequency |
47 to 53 Hz |
 |
Output |
Rating |
1/2/3/7.5/15/20 KVA, Single Phase 10/20/30/40/50/60/75/100/120/150/200/250/300/400/500 KVA, 3 Phase |
| |
|
Voltage |
220/230/240 Single Phase 380/400/415 V, 3 Φ |
| |
|
Regulation |
±1% for unbalanced load |
| |
|
Phase Dispacement |
120±1 deg for 100% unbalanced load |
| |
|
Power Factor |
0.8 |
| |
|
Crest Factor |
3:1 |
| |
|
Frequency
Wave Form
Harmonic Distortion |
50Hz±0.1%
Sine Wave
<3% THD for linear load
<5% THD for non-linear load
|
| |
|
Over Load |
110% for 30 minutes
125% for 10 minutes
150% for 60 seconds |
| |
|
Transient Response |
±5% for 100% step load change |
| |
|
Response Time |
Recover to ±1% within 5msec |
|
| |
| |
|