Three Phase (DC) Air Cooled - 5 - 2500 KVA
AAC mains voltage fluctuations are a common phenomenon in power supply system. Such fluctuations may result into erratic behavior, malfunction or even break down leading to expensive repairs, production loss and missed commitments.
PMDC Voltage Stabilisers are designed to ensure that their output voltage remain constant irrespective of the voltage swings in the incoming power supply.
Their high efficiency and the ability to withstand instant load variations make them an ideal choice for protection of expensive and sensitive equipment.
| Type | KVA Ratings | Model | Servo Motor | Input Voltage Range (VAC) |
Output Voltage (VAC) |
|---|---|---|---|---|---|
| Unbalance 3 Phase | 5 – 2000 KVA | SDA – XXX SDA – XXXX SDA – XXXXX |
PMDC Servo Motor | 340 - 480 | 415 |
a) Please contact our sales and application engineers for further guidance
b) Non-Standard Input Voltage Range and Output Voltages are also available on request
| Output Voltage Accuracy | 1% |
| Response Time | < 10 m.sec |
| Rate of Correction | Up to 105 V / Sec |
| Efficiency | Better than 98 %. |
| Frequency | 47 – 53 Hz. |
| Effect of Load Power Factor | Nil |
| Wave form Distortion | Nil (Same as input) |
| Harmonic Distortion | None |
| Unbalanced Line and Load | Independent phase sensing and control provides for 100 % load imbalance within the rating of equipment |
| MCB/MCCB/ACB # | At Incoming for Over Load and Short circuit protection. |
| Output Voltage Protection. | Electronics Adjustable Output Under and Over Volt. Alarm / time Delay Circuit, Per Phase Indications with Output Voltage Trip. |
| Servo Motor Protection | Voltage Cut-off for Servo Motor at Input Under/Over volts |
| Environment | Temperature range – 0 to 45 °C. Suitable for indoor Tropical use 90% RH (non-condensing) |
| IP class | IP21 |
| Color | RAL – 7035 (Grey) |
| MTBF | Mean Time Between Failure – Better than 43,800 Hrs |
| Life Expectancy | 20 to 25 Years. |
- Medical Diagnostic Equipment
- Electronic Equipment
- Lab Equipment
- Pharmaceuticals Machine
- Textile Machinery
- Process Controls
- Elevators
- Cold Storage
- Hospitals
- Residential
- High Torque Low Inertia Motor with Proportional Control.
- High Rate of Correction.
- Response time less than 10 m seconds.
- Low losses. Efficiency better than 98 %.
- Full function Auto / Manual & Lower Raise controls.
- Voltmeter for Input & Output Voltages.
- Output under & Over Voltage LED for Fault indication.
- Advanced electronic circuits to maintain constant output voltage even on DG.
- Phase missing / Reversal Protection
- Input Under and Over Voltage indication and Cut off
- Electronics Output Over Load.
- Ground Fault Monitoring with Trip and Indication.
- Output cut-off if Neutral is missing.
- High Earth – Neutral Voltage Cut off.
- High Low Frequency Cut off.
- Auto Start with time delay.
- Stabiliser By pass Switch
- Surge Protective Device 8/20 micro sec. as per IEC 61000-4-4 / 61000-4-5.
- Surge Suppressor (Metal Oxide Varistor).
- Other Color ( specify RAL shade number)
Typical schematics for product installation
- # Non-Standard KVA, Input Voltage Range and Output Voltages are also available on request.
- # NEELKANTH reserves the rights to amend design and specification without notice as continuous efforts are Made to Improve product performance.
- # Some of the features are optional depend on model and as per order.